MP panel filter ePM2.5 55%
APPLICATION
MP Panel filter is used as a pre-filter for air treatment cabinets, air conditioning systems and industrial systems.
CONSTRUCTION
MP Panel filter are pleated filters which are assembled within a moisture-resistant cardboard frame.
FILTER CLASS
ePM10 75%, ePM2,5 55%, ePM1 55% , ePM1 80% in compliance with ISO16890
SPECIFICATIONS
Application : Prefilters HVAC, industry,
Frame : Firm cardboard frame
Medium : Glassfiber
Filter class according to ISO 16890 : ePM10, ePM2,5, ePM1
Maximum final pressure drop : 450Pa
Maximum temperature : 70°C
Maximum relative humidity : 90%
INSTALLATION
- Ensure that the filter is fitted correctly:Suction side – clean air side
- Filter should be correctly installed: no leaks
- Gaskets should be completely undamaged
- Filter should be secured at four points
- Ensure that the filter medium is not folded double
- Take care to avoid damaging the filter during installation
- System should be run in for several hours to achieve the desired result
- Filter installation records; note the date, type and initial resistance.
MP panel dim. 305x490x23 mm. ORCON HRC-300/400
Item No.
MP/305X490X23-F6/SCH
Panelen met kartonnen frame/Normal/M6
ePM2.5 55%
HPQ dim. 288x592x292 mm
Item No.
HPQ-98-C/ES
MP panel dim. 237x417x45 mm.
Item No.
MP/237X417X45-M5
HLA filter dim. 457x457x68 mm. F9
Item No.
HLA1109DCCE
CS H13 dim. 592x592x292 mm PTFE media
Item No.
CS-H13-A/P1